- USD
- CNY
- HKD
- EUR
- العربية
- čeština
- dansk
- Deutsch
- Ελληνικά
- English
- Español
- Français
- ic
- Italiano
- Netherlands
- norsk Språk
- język polski
- pt
- Português
- 中文


DI571
Subscribe to get prices
Model: DI571
Order No: 3ABD10094782
SKU: 10000080660501
Size: 0.00 mm,0.00 mm,0.00 mm
Weight: 0.13kg
Brief Introduction
DI571
The DI571 is a digital input module with 8 digital input channels and input voltages ranging from 100V AC to 240V ACIsolation characteristics: Galvanic isolation between the channels and the rest of the module, the number of isolation groups is 8, 1 channel per groupPower Consumption: The current consumption from a 24V DC power supply is approximately 10mWeight: Approx. 135g1.Installation position: It can be installed horizontally or vertically, and the natural convection cooling cannot be obstructed by the cable tray or other components in the control cabinet.Input Voltage Range: 0V AC to 264V AC (47Hz to 63Hz)Input current: 6mA (159V AC, 50Hz) per channel at 25°C typical; >7mA(159V AC,60Hz)Input type: Type 1 according to EN 61131-2Signal range: Signal 0(max.) is 20V AC; 20V AC < U < 79V AC for Undefined signal, 79V AC for Signal 1 (min.) Input Delay: 15ms typical for Signal 0 -> 1; Signal 1 -> 0 typically has a value of 30ms1.Maximum permissible leakage current: 1mA with 2-wire proximity switchMaximum cable length: 500m for shielded cables and 300m for unshielded cablesEach channel has 1 yellow LED that lights up when the input signal is high (signal 1).With terminal strip wiring, there are many types of terminal blocks to choose from, such as TA563-9, TA563-11, TA564-9, TA564-11, TA565-9, TA565-11, etcFollowing the environmental conditions in the AC500-eCo system data, the operating temperature range is typically 0°C to +60°C; Storage temperature range from -40°C to +70°C; Relative humidity of 0 to 95% RH and non-condensing
Description
Isolation characteristics: Galvanic isolation between the channels and the rest of the module, the number of isolation groups is 8, 1 channel per group
Power Consumption: The current consumption from a 24V DC power supply is approximately 10m
Weight: Approx. 135g1.
Installation position: It can be installed horizontally or vertically, and the natural convection cooling cannot be obstructed by the cable tray or other components in the control cabinet.
Input Voltage Range: 0V AC to 264V AC (47Hz to 63Hz)
Input current: <5mA (40V AC) and >6mA (159V AC, 50Hz) per channel at 25°C typical; >7mA(159V AC,60Hz)
Input type: Type 1 according to EN 61131-2
Signal range: Signal 0(max.) is 20V AC; 20V AC < U < 79V AC for Undefined signal, 79V AC for Signal 1 (min.) Input Delay: 15ms typical for Signal 0 -> 1; Signal 1 -> 0 typically has a value of 30ms1.
Maximum permissible leakage current: 1mA with 2-wire proximity switch
Maximum cable length: 500m for shielded cables and 300m for unshielded cables
Each channel has 1 yellow LED that lights up when the input signal is high (signal 1).
With terminal strip wiring, there are many types of terminal blocks to choose from, such as TA563-9, TA563-11, TA564-9, TA564-11, TA565-9, TA565-11, etc
Following the environmental conditions in the AC500-eCo system data, the operating temperature range is typically 0°C to +60°C; Storage temperature range from -40°C to +70°C; Relative humidity of 0 to 95% RH and non-condensing