SIMATIC S7-1200, ANALOG INPUT, SM 1231RTD, 8 X AI RTD MODULE, |
Supply voltage |
24 V DC |
Yes |
Input current |
Current consumption, typ. |
40 mA |
from backplane bus 5 V DC, typ. |
80 mA |
Power losses |
Power loss, typ. |
1.5 W |
Analog inputs |
Number of analog inputs |
8; Resistance thermometer |
permissible input frequency for current input (destruction limit), max. |
± 35 V |
Technical unit for temperature measurement adjustable |
Degrees Celsius/degrees Fahrenheit |
Input ranges |
● Thermocouple |
No |
● Resistance thermometer |
Yes; Resistance-type transmitter: Pt10, Pt50, Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni200, Ni500, Ni1000, Cu10, Cu50, Cu100, LG-Ni1000 |
● Resistance |
Yes; 150 Ω, 300 Ω, 600 Ω |
Input ranges (rated values), resistance thermometer |
● Cu 10 |
Yes |
● Input resistance (Cu 10) |
10 Ω |
● Ni 100 |
Yes |
● Input resistance (Ni 100) |
100 Ω |
● Ni 1000 |
Yes |
● Input resistance (Ni 1000) |
1 000 Ω |
● LG-Ni 1000 |
Yes |
● Input resistance (LG-Ni 1000) |
1 000 Ω |
● Ni 120 |
Yes |
● Input resistance (Ni 120) |
120 Ω |
● Ni 200 |
Yes |
● Input resistance (Ni 200) |
200 Ω |
● Ni 500 |
Yes |
● Input resistance (Ni 500) |
500 Ω |
● Pt 100 |
Yes |
● Input resistance (Pt 100) |
100 Ω |
● Pt 1000 |
Yes |
● Input resistance (Pt 1000) |
1 000 Ω |
● Pt 200 |
Yes |
● Input resistance (Pt 200) |
200 Ω |
● Pt 500 |
Yes |
● Input resistance (Pt 500) |
500 Ω |
Input ranges (rated values), resistors |
● 0 to 150 ohms |
Yes |
● 0 to 300 ohms |
Yes |
● 0 to 600 ohms |
Yes |
Thermocouple (TC) |
Temperature compensation |
— Parameterizable |
No |
Analog outputs |
Number of analog outputs |
0 |
Analog value creation |
Measurement principle |
integrating |
Integration and conversion time/resolution per channel |
● Resolution with overrange (bit including sign), max. |
15 bit; + sign |
● Integration time, parameterizable |
No |
● Interference voltage suppression for interference frequency f1 in Hz |
85 dB at 50 / 60 / 400 Hz |
Errors/accuracies |
Temperature error (relative to input range), (+/-) |
25 °C ±0.1% to 55 °C ±0.2% total measurement range |
Repeat accuracy in steady state at 25 °C (relative to output area), (+/-) |
0.05 % |
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency |
● Common mode interference, min. |
120 dB |
Interrupts/diagnostics/status information |
Alarms |
● Alarms |
Yes |
● Diagnostic alarm |
Yes |
Diagnostic messages |
● Diagnostic functions |
Yes; Can be read out |
● Monitoring the supply voltage |
Yes |
● Wire break |
Yes |
Diagnostics indication LED |
● for status of the inputs |
Yes |
● for maintenance |
Yes |
Degree and class of protection |
Degree of protection to EN 60529 |
|
● IP20 |
Yes |
Standards, approvals, certificates |
CE mark |
Yes |
RCM (formerly C-TICK) |
Yes |
FM approval |
Yes |
Highest safety class achievable in safety mode |
● SIL according to IEC 61508:2010 |
none |
Climatic and mechanical conditions for storage and transport |
Climatic conditions for storage and transport |
Free fall |
— Drop height, max. (in packaging) |
0.3 m; five times, in dispatch package |
Temperature |
— Permissible temperature range |
-40 °C to +70 °C |
Air pressure acc. to IEC 60068-2-13 |
— Permissible air pressure |
1080 to 660 hPa |
Relative humidity |
— Permissible range (without condensation) at 25 °C |
95 % |
Mechanical and climatic conditions during operation |
Climatic conditions in operation |
Temperature |
— Permissible temperature range |
-20 °C to +60 °C horizontal mounting, -20 °C to 50 °C vertical mounting, 95% humidity, non-condensing |
Air pressure acc. to IEC 60068-2-13 |
— Permissible air pressure |
1080 to 795 hPa |
Pollutant concentrations |
— SO2 at RH < 60% without condensation |
S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free |
Connection method |
required front connector |
Yes |
Mechanics/material |
Type of housing (front) |
|
● plastic |
Yes |
Dimensions |
Width |
70 mm |
Height |
100 mm |
Depth |
75 mm |
Weights |
Weight, approx. |
220 g |
last modified: |
13.10.2014 |