SIMATIC DP, 5 ELECTRON. MODULES FOR ET 200S, 4 DO STANDARD DC 24V/2A, 15 MM WIDTH 5 PIECES PER PACKAGING UNIT |
Supply voltage |
Reverse voltage protection |
Yes; when using the same load voltage as on the power module |
Load voltage L+ |
● Rated value (DC) |
24 V; From power module |
● Reverse polarity protection |
Yes |
Input current |
from load voltage L+ (without load), max. |
10 mA; Per channel |
from backplane bus 3.3 V DC, max. |
10 mA |
Power losses |
Power loss, typ. |
1.6 W |
Address area |
Address space per module |
● with packing |
4 bit |
● without packing |
1 byte |
Digital outputs |
Number of digital outputs |
4 |
short-circuit protection |
Yes |
● Response threshold, typ. |
2.8 to 7.2 A |
Limitation of inductive shutdown voltage to |
Typ. L+ (-55 to -60 V) |
Controlling a digital input |
Yes |
Switching capacity of the outputs |
● Lamp load, max. |
10 W |
Load resistance range |
● lower limit |
12 Ω |
● upper limit |
3 400 Ω |
Output voltage |
● for signal "1", min. |
L+ (-1.0 V) |
Output current |
● for signal "1" rated value |
2 A |
● for signal "1" permissible range for 0 to 60 °C, min. |
7 mA |
● for signal "1" permissible range for 0 to 60 °C, max. |
2.4 A |
● for signal "0" residual current, max. |
0.5 mA |
Output delay with resistive load |
● "0" to "1", max. |
50 µs; Typ. 45 µs |
● "1" to "0", max. |
120 µs; Typ. 90 µs |
Parallel switching of 2 outputs |
● for increased power |
No |
● for redundant control of a load |
Yes; per module |
Switching frequency |
● with resistive load, max. |
1 000 Hz |
● with inductive load, max. |
2 Hz; At 0.5 H |
● on lamp load, max. |
10 Hz |
Aggregate current of outputs (per group) |
all mounting positions |
— up to 60 °C, max. |
4 A |
vertical installation |
— up to 40 °C, max. |
4 A; At 55 °C and 24 V DC |
Cable length |
● Cable length, shielded, max. |
1 000 m |
● Cable length unshielded, max. |
600 m |
Isochronous mode |
Isochronous operation (application synchronized up to terminal) |
Yes |
Interrupts/diagnostics/status information |
Diagnostic messages |
● Diagnostic functions |
No |
Diagnostics indication LED |
● Status indicator digital output (green) |
Yes |
Parameter |
Remark |
1 byte |
Galvanic isolation |
Galvanic isolation digital outputs |
● between the channels |
No |
● between the channels and the backplane bus |
Yes |
Isolation |
Isolation checked with |
500 V DC |
Dimensions |
Width |
15 mm |
Height |
81 mm |
Depth |
52 mm |
Weights |
Weight, approx. |
40 g |
last modified: |
25.09.2014 |