ET200S Price List
ET200S 6ES7134-4FB52-0AB0

6ES7134-4FB52-0AB0

Subscribe to get prices

Model: 6ES7134-4FB52-0AB0

Order No:

SKU: 10000003878001

Size: 0.00 cm,0.00 cm,0.00 cm

Weight: 2.00kg

In Stock

Brief Introduction

6ES7134-4FB52-0AB0

*** Spare part *** SIMATIC DP, Electronics module ET 200S: 2 AI High Speed U, 15 bit, 15 mm width, Cycle time of module: 0.1 ms, with SF LED (group fault)

Description

  
 
Artikelnummer 6ES7134-4FB52-0AB0
Supply voltage
Load voltage L+
● Rated value (DC) 24 V
● Reverse polarity protection Yes
Input current
from load voltage L+ (without load), max. 80 mA
from backplane bus 3.3 V DC, max. 10 mA
Power losses
Power loss, typ. 1.9 W
Address area
Address space per module
● Address space per module, max. 4 byte
Analog inputs
Number of analog inputs 2
permissible input voltage for voltage input (destruction limit), max. 35 V
Cycle time (all channels) max. 250 µs
Input ranges
● Voltage Yes
● Current No
● Thermocouple No
● Resistance thermometer No
● Resistance No
Input ranges (rated values), voltages
● 1 to 5 V Yes
● Input resistance (1 to 5 V) 120 kΩ
● -10 V to +10 V Yes
● Input resistance (-10 V to +10 V) 120 kΩ
● -2.5 V to +2.5 V Yes
● Input resistance (-2.5 V to +2.5 V) 120 kΩ
● -5 V to +5 V Yes
● Input resistance (-5 V to +5 V) 120 kΩ
Cable length
● Cable length, shielded, max. 200 m
Analog value creation
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 16 bit
Smoothing of measured values
● Parameterizable Yes
● Step: None Yes
● Step: low Yes
● Step: Medium Yes
● Step: High Yes
Encoder
Connection of signal encoders
● for voltage measurement Yes
Errors/accuracies
Linearity error (relative to input range), (+/-) 0.03 %
Temperature error (relative to input range), (+/-) 0.01 %/K
Crosstalk between the inputs, min. -50 dB
Repeat accuracy in steady state at 25 °C (relative to input area), (+/-) 0.1 %
Operational limit in overall temperature range
● Voltage, relative to input area, (+/-) 0.3 %
Basic error limit (operational limit at 25 °C)
● Voltage, relative to input area, (+/-) 0.2 %
Isochronous mode
Isochronous operation (application synchronized up to terminal) Yes
Interrupts/diagnostics/status information
Alarms
● Hardware interrupt Yes
Diagnostic messages
● Diagnostic functions Yes
● Diagnostic information readable Yes
● Wire break Yes
● Group error Yes
● Overflow/underflow Yes
Diagnostics indication LED
● Group error SF (red) Yes
Galvanic isolation
Galvanic isolation analog inputs
● between the channels No
● between the channels and the backplane bus Yes
● between the channels and the load voltage L+ Yes
Dimensions
Width 15 mm
Height 81 mm
Depth 52 mm
Weights
Weight, approx. 45 g