Supply voltage |
Load voltage L+ |
● Rated value (DC) |
24 V |
● Reverse polarity protection |
Yes |
Input current |
from load voltage L+ (without load), max. |
80 mA |
from backplane bus 3.3 V DC, max. |
10 mA |
Power losses |
Power loss, typ. |
1.9 W |
Address area |
Address space per module |
● Address space per module, max. |
4 byte |
Analog inputs |
Number of analog inputs |
2 |
permissible input voltage for voltage input (destruction limit), max. |
35 V |
Cycle time (all channels) max. |
250 µs |
Input ranges |
● Voltage |
Yes |
● Current |
No |
● Thermocouple |
No |
● Resistance thermometer |
No |
● Resistance |
No |
Input ranges (rated values), voltages |
● 1 to 5 V |
Yes |
● Input resistance (1 to 5 V) |
120 kΩ |
● -10 V to +10 V |
Yes |
● Input resistance (-10 V to +10 V) |
120 kΩ |
● -2.5 V to +2.5 V |
Yes |
● Input resistance (-2.5 V to +2.5 V) |
120 kΩ |
● -5 V to +5 V |
Yes |
● Input resistance (-5 V to +5 V) |
120 kΩ |
Cable length |
● Cable length, shielded, max. |
200 m |
Analog value creation |
Integration and conversion time/resolution per channel |
● Resolution with overrange (bit including sign), max. |
16 bit |
Smoothing of measured values |
● Parameterizable |
Yes |
● Step: None |
Yes |
● Step: low |
Yes |
● Step: Medium |
Yes |
● Step: High |
Yes |
Encoder |
Connection of signal encoders |
● for voltage measurement |
Yes |
Errors/accuracies |
Linearity error (relative to input range), (+/-) |
0.03 % |
Temperature error (relative to input range), (+/-) |
0.01 %/K |
Crosstalk between the inputs, min. |
-50 dB |
Repeat accuracy in steady state at 25 °C (relative to input area), (+/-) |
0.1 % |
Operational limit in overall temperature range |
● Voltage, relative to input area, (+/-) |
0.3 % |
Basic error limit (operational limit at 25 °C) |
● Voltage, relative to input area, (+/-) |
0.2 % |
Isochronous mode |
Isochronous operation (application synchronized up to terminal) |
Yes |
Interrupts/diagnostics/status information |
Alarms |
● Hardware interrupt |
Yes |
Diagnostic messages |
● Diagnostic functions |
Yes |
● Diagnostic information readable |
Yes |
● Wire break |
Yes |
● Group error |
Yes |
● Overflow/underflow |
Yes |
Diagnostics indication LED |
● Group error SF (red) |
Yes |
Galvanic isolation |
Galvanic isolation analog inputs |
● between the channels |
No |
● between the channels and the backplane bus |
Yes |
● between the channels and the load voltage L+ |
Yes |
Dimensions |
Width |
15 mm |
Height |
81 mm |
Depth |
52 mm |
Weights |
Weight, approx. |
45 g |