SIMATIC DP, ELECTRONIC MODULE ET200S: 2AI HIGH SPEED I-2WIRE, 0 - 20MA, 4 - 20MA, 15BIT, 15 MM WIDTH, FOR 2-WIRE TRANSDUCER, CYCLE TIME OF THE MOD.: 0.1MS, WITH LED SF (GROUP FAULT) |
Supply voltage |
Load voltage L+ |
● Rated value (DC) |
24 V |
● Short-circuit protection |
Yes |
● Reverse polarity protection |
Yes |
Input current |
from load voltage L+ (without load), max. |
225 mA |
from backplane bus 3.3 V DC, max. |
10 mA |
Output voltage |
Power supply to the transmitters |
● present |
Yes |
● short-circuit proof |
Yes |
Power loss |
Power loss, typ. |
2.5 W |
Address area |
Address space per module |
● Address space per module, max. |
4 byte |
Analog inputs |
Number of analog inputs |
2 |
Cycle time (all channels) max. |
0.25 ms |
Input ranges |
● Voltage |
No |
● Current |
Yes |
● Thermocouple |
No |
● Resistance thermometer |
No |
● Resistance |
No |
Input ranges (rated values), currents |
● 0 to 20 mA |
Yes |
● Input resistance (0 to 20 mA) |
106 Ω |
● 4 to 20 mA |
Yes |
Cable length |
● Cable length, shielded, max. |
200 m |
Analog value generation |
Integration and conversion time/resolution per channel |
● Resolution with overrange (bit including sign), max. |
16 bit |
Smoothing of measured values |
● parameterizable |
Yes |
● Step: None |
Yes; 1 |
● Step: Low |
Yes; 4 |
● Step: Medium |
Yes; 16 |
● Step: High |
Yes; 32 |
Encoder |
Connection of signal encoders |
● for current measurement as 2-wire transducer |
Yes |
Errors/accuracies |
Linearity error (relative to input range), (+/-) |
0.03 % |
Temperature error (relative to input range), (+/-) |
0.01 %/K |
Crosstalk between the inputs, min. |
50 dB |
Repeat accuracy in steady state at 25 °C (relative to input area), (+/-) |
0.1 % |
Operational error limit in overall temperature range |
● Current, relative to input area, (+/-) |
0.3 % |
Basic error limit (operational limit at 25 °C) |
● Current, relative to input area, (+/-) |
0.2 % |
Isochronous mode |
Isochronous mode (application synchronized up to terminal) |
Yes |
Interrupts/diagnostics/status information |
Alarms |
● Hardware interrupt |
Yes |
Diagnostic messages |
● Diagnostic functions |
Yes |
● Wire-break |
Yes; at 4 to 20 mA |
● Group error |
Yes |
● Overflow/underflow |
Yes |
Diagnostics indication LED |
● Group error SF (red) |
Yes |
Parameter |
Diagnostics wire break |
At 4 to 20 mA |
Measurement type/range |
4 to 20 mA, 0 to 20 mA |
Interference frequency suppression |
No |
Group diagnostics |
1 |
Overflow/underflow |
1 |
Galvanic isolation |
Galvanic isolation analog inputs |
● between the channels |
No |
● between the channels and the backplane bus |
Yes |
● between the channels and the load voltage L+ |
Yes |
Permissible potential difference |
between MANA and M internally (UISO) |
75 VDC / 60 VAC |
Dimensions |
Width |
15 mm |
Height |
81 mm |
Depth |
52 mm |