SIMATIC DP, ELECTRONIC MODULE 2 AI U HIGH FEATURE FOR ET 200S, 15 MM WIDE, CYCLE TIME PER MODULE: 0.5MS, +/-10V; 15 BI + SIGN, +/-5V;15BIT+SIGN, 1..5V; 15BIT, OPERATIONAL LIMITS +/-0.1% WITH LED SF (GROUP FAULT) |
Supply voltage |
Load voltage L+ |
● Rated value (DC) |
24 V |
● Reverse polarity protection |
Yes |
Input current |
from load voltage L+ (without load), max. |
55 mA |
from backplane bus 3.3 V DC, max. |
10 mA |
Output voltage |
Power supply to the transmitters |
● present |
No |
Power loss |
Power loss, typ. |
0.85 W |
Address area |
Address space per module |
● Address space per module, max. |
4 byte |
Analog inputs |
Number of analog inputs |
2 |
permissible input voltage for voltage input (destruction limit), max. |
35 V; 35 V continuous; 75 V for max. 1 ms |
Cycle time (all channels) max. |
0.5 ms; 0.5 ms for 2 channels without noise suppression, 18 / 21 ms per channel with noise suppression |
Input ranges |
● Voltage |
Yes |
● Current |
No |
● Thermocouple |
No |
● Resistance thermometer |
No |
● Resistance |
No |
Input ranges (rated values), voltages |
● 1 to 5 V |
Yes |
● Input resistance (1 to 5 V) |
800 kΩ |
● -10 V to +10 V |
Yes |
● Input resistance (-10 V to +10 V) |
800 kΩ |
● -5 V to +5 V |
Yes |
● Input resistance (-5 V to +5 V) |
800 kΩ |
Cable length |
● Cable length, shielded, max. |
200 m |
Analog value generation |
Integration and conversion time/resolution per channel |
● Resolution with overrange (bit including sign), max. |
16 bit; 0 to 5 V: 15 bits, +/-10 V: 16 bits, +/-5 V: 16 bits |
● Integration time, parameterizable |
Yes |
● Interference voltage suppression for interference frequency f1 in Hz |
60 / 50 Hz / no |
● Conversion time (per channel) |
0.04 ms; Without noise suppression 17/20 ms per channel with error |
Smoothing of measured values |
● parameterizable |
Yes; In 4 stages: 1 x, 4 x, 16 x, 32 x cycle time |
● Step: None |
Yes; 1 x |
● Step: low |
Yes; 4 x |
● Step: Medium |
Yes; 16 x |
● Step: High |
Yes; 32 x |
Encoder |
Connection of signal encoders |
● for voltage measurement |
Yes |
Errors/accuracies |
Linearity error (relative to input range), (+/-) |
0.01 % |
Temperature error (relative to input range), (+/-) |
0.003 %/K |
Crosstalk between the inputs, min. |
-100 dB |
Repeat accuracy in steady state at 25 °C (relative to input area), (+/-) |
0.01 % |
Operational error limit in overall temperature range |
● Voltage, relative to input area, (+/-) |
0.1 %; 0.2% without interference frequency suppression |
Basic error limit (operational limit at 25 °C) |
● Voltage, relative to input area, (+/-) |
0.05 %; 0.1% without interference frequency suppression |
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency |
● Series mode interference (peak value of interference < rated value of input range), min. |
90 dB |
● Common mode interference (USS < 2.5 V) , min. |
100 dB |
Isochronous mode |
Isochronous mode (application synchronized up to terminal) |
Yes |
Interrupts/diagnostics/status information |
Alarms |
● Hardware interrupt |
Yes |
Diagnostic messages |
● Diagnostic functions |
Yes |
● Wire-break |
Yes; Measuring range 1 to 5 V only |
● Group error |
Yes |
● Overflow/underflow |
Yes |
Diagnostics indication LED |
● Group error SF (red) |
Yes |
Parameter |
Remark |
12 bytes, 4 bytes in compatibility mode |
Measurement type/range |
deactivated / +/-5 V / 1 to 5 V / +/-10 V |
Group diagnostics |
Disable / enable |
Overflow/underflow |
Disable / enable |
Galvanic isolation |
Galvanic isolation analog inputs |
● between the channels |
No; however, increased permissible potential difference between the inputs. |
● between the channels and the backplane bus |
Yes |
● between the channels and the load voltage L+ |
Yes |
Permissible potential difference |
between the inputs (UCM) |
140 V DC/100 V AC |
Isolation |
Isolation tested with |
500 V DC |
Dimensions |
Width |
15 mm |
Height |
81 mm |
Depth |
52 mm |
Weights |
Weight, approx. |
45 g |
last modified: |
31.07.2014 |