SIMATIC DP, ET 200ECO PN, 8 AI (4 U/I + 4 RTD/TC); 8XM12, DEGREE OF PROTECTION IP67 |
General information |
Vendor identification (VendorID) |
002AH |
Device identifier (DeviceID) |
0306H |
Supply voltage |
24 V DC |
Yes |
permissible range, lower limit (DC) |
20.4 V |
permissible range, upper limit (DC) |
28.8 V |
Reverse polarity protection |
Yes |
Input current |
Current consumption, typ. |
110 mA |
Encoder supply |
Number of outputs |
4 |
24 V encoder supply |
● Short-circuit protection |
Yes; Electronic at 1.4 A |
● Output current, max. |
1 A |
Power loss |
Power loss, typ. |
2.8 W |
Analog inputs |
Number of analog inputs |
8 |
Number of analog inputs for voltage/current measurement |
4 |
Number of analog inputs for resistance/resistance thermometer measurement |
4 |
permissible input voltage for voltage input (destruction limit), max. |
28.8 V permanent, 35 V for max. 500 ms |
Input ranges (rated values), voltages |
● 0 to +10 V |
Yes |
● 1 to 5 V |
Yes |
● -10 V to +10 V |
Yes |
● -80 mV to +80 mV |
Yes |
Input ranges (rated values), currents |
● 0 to 20 mA |
Yes |
● -20 to +20 mA |
Yes |
● 4 to 20 mA |
Yes |
Input ranges (rated values), thermocouples |
● Type E |
Yes |
● Type J |
Yes |
● Type K |
Yes |
● Type N |
Yes |
Input ranges (rated values), resistance thermometers |
● Ni 100 |
Yes |
● Ni 1000 |
Yes |
● Ni 120 |
Yes |
● Ni 200 |
Yes |
● Ni 500 |
Yes |
● Pt 100 |
Yes |
● Pt 1000 |
Yes |
● Pt 200 |
Yes |
● Pt 500 |
Yes |
Input ranges (rated values), resistors |
● 0 to 150 Ohm |
Yes |
● 0 to 300 Ohm |
Yes |
● 0 to 600 Ohm |
Yes |
● 0 to 3000 Ohm |
Yes |
Thermocouple (TC) |
Temperature compensation |
— parameterizable |
Yes |
— internal temperature compensation |
Yes |
— external temperature compensation with compensations socket |
Yes |
Cable length |
● Cable length, shielded, max. |
30 m |
Analog value generation |
Analog value display |
SIMATIC S7 format |
Measurement principle |
integrating |
Integration and conversion time/resolution per channel |
● Resolution (incl. overrange) |
15 bits + sign |
● Integration time, parameterizable |
Yes |
● Integration time, ms |
2/16.67/20/100 ms |
● Interference voltage suppression for interference frequency f1 in Hz |
500 / 60 / 50 / 10 Hz |
● Conversion time (per channel) |
4 / 19 / 22 / 102 ms |
Smoothing of measured values |
● parameterizable |
Yes |
● Step: None |
Yes; 1 x cycle time |
● Step: Low |
Yes; 4 x cycle time |
● Step: Medium |
Yes; 16 x cycle time |
● Step: High |
Yes; 64 x cycle time |
Encoder |
Number of connectable encoders, max. |
8 |
Connection of signal encoders |
● for voltage measurement |
Yes |
● for current measurement as 2-wire transducer |
Yes |
● for current measurement as 4-wire transducer |
Yes |
● for resistance measurement with two-wire connection |
Yes |
● for resistance measurement with three-wire connection |
Yes |
● for resistance measurement with four-wire connection |
Yes |
Errors/accuracies |
Linearity error (relative to input range), (+/-) |
0.01 % |
Temperature error (relative to input range), (+/-) |
U: 0.0035%/°C; I:0.006%/°C; RTD: 0.0005%/°C; TC: 0.0035%/°C |
Crosstalk between the inputs, min. |
85 dB |
Repeat accuracy in steady state at 25 °C (relative to input area), (+/-) |
0.008 % |
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency |
● Series mode interference (peak value of interference < rated value of input range), min. |
46 dB |
● Common mode interference, min. |
70 dB |
Interfaces |
Transmission procedure |
100BASE-TX |
Transmission rate, max. |
100 Mbit/s |
PROFINET IO |
● Number of PROFINET interfaces |
1 |
● Autocrossing |
Yes |
● automatic detection of transmission rate |
Yes |
● integrated switch |
Yes |
PROFINET IO Device |
— IRT with the option "high flexibility", supported |
Yes |
— Prioritized startup |
Yes |
Protocols |
PROFINET IO |
Yes |
PROFINET CBA |
No |
PROFIsafe |
No |
Protocols (Ethernet) |
● SNMP |
Yes |
● DCP |
Yes |
● LLDP |
Yes |
● ping |
Yes |
● ARP |
Yes |
Interrupts/diagnostics/status information |
Status indicator |
Yes |
Alarms |
● Diagnostic alarm |
Yes |
Diagnostic messages |
● Diagnostic functions |
Yes |
● Diagnostic information readable |
Yes |
● Monitoring the supply voltage |
Yes; Green "ON" LED |
● Short-circuit encoder supply |
Yes; per module |
● Group error |
Yes; Red/yellow "SF/MT" LED |
● Overflow/underflow |
Yes |
Galvanic isolation |
between the load voltages |
Yes |
between load voltage and all other switching components |
No |
between Ethernet and electronics |
Yes |
Galvanic isolation analog inputs |
● between the channels |
No |
Permissible potential difference |
between inputs and MANA (UCM) |
10 Vpp AC |
Isolation |
tested with |
● 24 V DC circuits |
500 V |
● Interface |
1 500 V; According to IEEE 802.3 |
Degree and class of protection |
IP65 |
Yes |
IP66 |
Yes |
IP67 |
Yes |
Connection method |
M12 |
Yes |
Dimensions |
Width |
60 mm |
Height |
175 mm |
Depth |
49 mm |
Weights |
Weight (without packaging) |
930 g |
last modified: |
21.08.2014 |