SIMATIC DP, ET 200ECO PN, 4 AO U/I; 4 X M12, DEGREE OF PROTECTION IP67 |
|
General information |
Vendor identification (VendorID) |
002AH |
Device identifier (DeviceID) |
0306H |
Supply voltage |
24 V DC |
Yes |
permissible range, lower limit (DC) |
20.4 V |
permissible range, upper limit (DC) |
28.8 V |
Reverse polarity protection |
Yes |
Input current |
Current consumption, typ. |
280 mA |
Encoder supply |
Number of outputs |
4 |
24 V encoder supply |
short-circuit protection |
Yes; Electronic at 1.4 A |
Output current, max. |
1 A |
Power losses |
Power loss, typ. |
5.5 W |
Analog outputs |
Number of analog outputs |
4 |
Voltage output, short-circuit protection |
Yes |
Voltage output, short-circuit current, max. |
30 mA |
Current output, no-load voltage, max. |
20 V |
Output ranges, voltage |
0 to 10 V |
Yes |
1 to 5 V |
Yes |
-10 to +10 V |
Yes |
Output ranges, current |
0 to 20 mA |
Yes |
-20 to +20 mA |
Yes |
4 to 20 mA |
Yes |
Connection of actuators |
for voltage output two-wire connection |
Yes |
for current output two-wire connection |
Yes |
Load impedance (in rated range of output) |
with voltage outputs, min. |
1 kΩ |
with voltage outputs, capacitive load, max. |
1 µF |
with current outputs, max. |
600 Ω |
with current outputs, inductive load, max. |
1 mH |
Destruction limits against externally applied voltages and currents |
Voltages at the outputs towards MANA |
28.8 V permanent, 35 V for max. 500 ms |
Cable length |
Cable length, shielded, max. |
30 m |
Analog value creation |
Analog value display |
SIMATIC S7 format |
Measurement principle |
Resistor network |
Integrations and conversion time/resolution per channel |
Resolution (incl. overrange) |
15 bits + sign |
Conversion time (per channel) |
1 ms |
Settling time |
for resistive load |
2 ms |
for capacitive load |
1.8 ms |
for inductive load |
2 ms |
Errors/accuracies |
Output ripple (based on output area, bandwidth 0 to 50 kHz), (+/-) |
U: ±0.6 mVrms; I: ±0.4 nArms |
Linearity error (relative to output range), (+/-) |
0.02 % |
Crosstalk between the outputs, min. |
70 dB |
Repeat accuracy in steady state at 25 °C (relative to output area), (+/-) |
0.0080 % |
Interfaces |
Transmission procedure |
100BASE-TX |
Transmission rate, max. |
100 Mbit/s |
Supports protocol for PROFINET IO |
Number of PROFINET interfaces |
1 |
Autocrossing |
Yes |
Automatic detection of transmission speed |
Yes |
Integrated switch |
Yes |
PROFINET IO Device |
IRT with the option "high flexibility" supported |
Yes |
Prioritized startup |
Yes |
Protocols |
Supports protocol for PROFINET IO |
Yes |
PROFINET CBA |
No |
Supports protocol for PROFIsafe |
No |
Protocols (Ethernet) |
SNMP |
Yes |
DCP |
Yes |
LLDP |
Yes |
ping |
Yes |
ARP |
Yes |
Interrupts/diagnostics/status information |
Status indicator |
Yes |
Substitute values connectable |
Yes |
Alarms |
Diagnostic alarm |
Yes |
Diagnostic messages |
Diagnostic functions |
Yes |
Diagnostic information readable |
Yes |
Monitoring the supply voltage |
Yes; Green "ON" LED |
Wire break |
Yes; Channel-by-channel with current output |
Short circuit |
Yes; Channel-by-channel with voltage output |
Group error |
Yes; Red/yellow "SF/MT" LED |
Galvanic isolation |
between the load voltages |
Yes |
between load voltage and all other switching components |
No |
between Ethernet and electronics |
Yes |
Galvanic isolation analog outputs |
between the channels |
No |
Permissible potential difference |
between M internally and the outputs |
10 Vpp AC |
Degree and class of protection |
IP65 |
Yes |
IP66 |
Yes |
IP67 |
Yes |
Connection method |
M12 |
Yes |
Dimensions |
Width |
60 mm |
Height |
175 mm |
Depth |
49 mm |
Weights |
Weight (without packaging) |
930 g |
Status |
May 26, 2014 |