SIMATIC DP, ELECTRONIC MODULE FOR ET200PRO 8 DI DC 24V, MODULE DIAGNOSTICS; INCLUSIVE BUS MODULE CONNECTING MODULE IO 6ES7194-4..00-0AA0 MUST BE ORDERED SEPERATELY |
FH technology |
Module for failsafe applications |
No |
Supply voltage |
24 V DC |
Yes |
permissible range, lower limit (DC) |
20.4 V |
permissible range, upper limit (DC) |
28.8 V |
Reverse polarity protection |
Yes; Against destruction; encoder power supply outputs applied with reversed polarity |
Input current |
from backplane bus 3.3 V DC, max. |
20 mA |
from supply voltage 1L+, max. |
20 mA |
Encoder supply |
Number of outputs |
8 |
short-circuit protection |
Yes; per module, electronic |
Output current |
● up to 55 °C, max. |
1 A |
Power losses |
Power loss, typ. |
2.5 W |
Address area |
Occupied address area |
● Inputs |
1 byte |
Digital inputs |
Number of digital inputs |
8 |
Input characteristic curve in accordance with IEC 61131, type 1 |
Yes |
Input characteristic curve in accordance with IEC 61131, type 2 |
No |
Number of simultaneously controllable inputs |
all mounting positions |
— up to 55 °C, max. |
8 |
Input voltage |
● Type of input voltage |
DC |
● Rated value (DC) |
24 V |
● for signal "0" |
-3 to +5V |
● for signal "1" |
13 to 30 V |
Input current |
● for signal "1", typ. |
7 mA |
Input delay (for rated value of input voltage) |
for standard inputs |
— Parameterizable |
No |
— at "0" to "1", min. |
1.2 ms |
— at "0" to "1", max. |
4.8 ms |
— at "1" to "0", min. |
1.2 ms |
— at "1" to "0", max. |
4.8 ms |
Cable length |
● Cable length, shielded, max. |
30 m |
● Cable length unshielded, max. |
30 m |
Encoder |
Connectable encoders |
● 2-wire sensor |
Yes |
— Permissible quiescent current (2-wire sensor), max. |
1.5 mA |
Isochronous mode |
Isochronous operation (application synchronized up to terminal) |
No |
Interrupts/diagnostics/status information |
Diagnostic messages |
● Diagnostic functions |
Yes |
● Diagnostic information readable |
Yes |
● Short circuit |
Yes; Sensor supply to M; module by module |
Diagnostics indication LED |
● Group error SF (red) |
Yes |
● Status indicator digital input (green) |
Yes; Per channel |
Parameter |
Diagnosis: short circuit |
Sensor supply to M; module by module |
Galvanic isolation |
between backplane bus and all other circuit components |
Yes |
Galvanic isolation digital inputs |
● between the channels |
No |
● between the channels and the backplane bus |
Yes |
Permissible potential difference |
between different circuits |
75 VDC / 60 VAC |
Isolation |
Isolation checked with |
500 V DC |
Degree and class of protection |
Degree of protection to EN 60529 |
|
● IP65 |
Yes |
● IP66 |
Yes |
● IP67 |
Yes |
Dimensions |
Width |
45 mm |
Height |
130 mm |
Depth |
35 mm |
Weights |
Weight, approx. |
140 g |
last modified: |
13.10.2014 |