SIMATIC DP, ELECTRONIC MODULES FOR ET200PRO 8 DI DC 24V HIGH FEATURE, CHANNEL DIAGNOSTICS; SHORT CIRCUIT AND WIRE BREAK; INCLUSIVE BUS MODULE CONNECTING MODULE IO 6ES7194-4..00-0AA0 MUST BE ORDERED SEPERATELY |
|
FH technology |
Module for failsafe applications |
No |
Supply voltage |
24 V DC |
Yes |
permissible range, lower limit (DC) |
20.4 V |
permissible range, upper limit (DC) |
28.8 V |
Reverse polarity protection |
Yes; against destruction; load increasing |
Input current |
from backplane bus 3.3 V DC, max. |
40 mA |
from supply voltage 1L+, max. |
20 mA |
Encoder supply |
|
8 |
|
Yes |
Output current |
up to 55 °C, max. |
1 A |
Power losses |
Power loss, typ. |
2.5 W |
Address area |
Occupied address area |
Inputs |
1 byte |
Digital inputs |
Number of digital inputs |
8 |
Input characteristic curve in accordance with IEC 61131, type 1 |
No |
Input characteristic curve in accordance with IEC 61131, type 2 |
Yes |
Number of simultaneously controllable inputs |
all mounting positions |
up to 55 °C, max. |
8 |
Input voltage |
Type of input voltage |
DC |
Rated value, DC |
24 V |
for signal "0" |
-3 to +5 V |
for signal "1" |
11 to 30 V |
Input current |
for signal "1", typ. |
7 mA |
Input delay (for rated value of input voltage) |
for standard inputs |
Parameterizable |
Yes |
at "0" to "1", min. |
0.5 ms |
at "0" to "1", max. |
20 ms |
at "1" to "0", min. |
0.5 ms |
at "1" to "0", max. |
20 ms |
Cable length |
|
30 m |
|
30 m |
Encoder |
Connectable encoders |
2-wire sensor |
Yes |
Permissible quiescent current (2-wire sensor), max. |
1.5 mA |
Isochronous mode |
Isochronous operation (application synchronized up to terminal) |
No |
Interrupts/diagnostics/status information |
Diagnostic messages |
Diagnostic functions |
Yes; channel by channel, parameterizable |
Diagnostic information readable |
Yes |
Wire break |
Yes; Monitoring, I < 0.3 mA |
Short circuit |
Yes |
Diagnostics indication LED |
Group error SF (red) |
Yes |
Status indicator digital input (green) |
Yes; Per channel |
Parameter |
Diagnostic alarm |
Yes |
Hardware interrupt |
for 6 channels |
Diagnosis: wire break |
channel by channel |
Diagnosis: short circuit |
channel by channel |
Galvanic isolation |
between backplane bus and all other circuit components |
Yes |
Galvanic isolation digital inputs |
between the channels |
No |
between the channels and the backplane bus |
Yes |
Degree and class of protection |
IP65 |
Yes |
IP66 |
Yes |
IP67 |
Yes |
Dimensions |
Width |
45 mm |
Height |
130 mm |
Depth |
35 mm; without terminal module |
Weights |
Weight, approx. |
140 g |
Status |
May 9, 2014 |