PSTX570-600-70
Subscribe to get prices
Model: PSTX570-600-70
Order No: 1SFA898217R7000
SKU: 10000006542501
Size: 361.00 mm,493.00 mm,282.00 mm
Weight: 27.00KG
Brief Introduction
PSTX570-600-70
Technical parametersRated Operating Voltage:208 ... 690 V ACRated control supply voltage (U.)s):100 ... 250 V ACRated control circuit voltage (Uc):24 V DCRated Frequency (f):50/60 HzMain Circuit 50 / 60 HzRated Operating Power - Coaxial Connection (PE):(230 V) 160 kW(400 V) 315 kW(500 V) 400 kW(690 V) 560 kWRated Operating Current - Coaxial Connection (IE):570 ARated Operating Power - Inner Delta Connection:at 230 V 295 kWat 400 V 540 kWat 500 V 700 kWat 690 V 960 kWRated Operating Current - Inner Delta Connection:987 APercentage of Safety Factor:100 %Overload Protection:Built-in electronic overload protectionIntegrated Electronic Overload:YesStarting capacity at maximum rated current Ie:4xIe for 10sSlope Time:1 ... 120 second [unit of time]Initial voltage at start-up:10 ... 99 %Special Buck Ramps:100 ... 10 %Inner triangle connection switch:beRunning Signal Relay:beBypass Signal Relay:YesFault Signal Relays:YesOverload Signal Relay:beReady to start/standby signal indication ON (LED):GreenOperational signal indication R (LED):GreenProtection Signal Indication (LED):YellowFault Signal Indication (LED):RedCommunication:Modbus-RTU; Modbus-TCP; Ethernet-IP; EtherCAT; DeviceNet; CANopen; Profibus; Profinet; BACnet-IP; BACnet-MSTPIngress Protection:acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00Terminal Type:Main Circuit: BarsControl circuit connection capacity:Rigid 1 x 2.5 mm²Power supply circuit connection capacity:Rigid 1 x 2.5 mm²Tightening torque:Main Circuit 35 N·mProduct range:PSTX570Function:Auto phase sequence detectionAutomatic restartCurrent limitCurrent limit rampDual current limitDynamic brakeElectricity meteringElectronic overload Time-to-coolEmergency modeEvent logShow moreProtection Functions:Bypass open protection; Current imbalance protection; Current underload protection; Dual overload (separate overload for start and run); Earth fault protection / ground fault protection; Electronic overload protection, EOL; Extension IO failure protection; Fieldbus failure protection; HMI failure protection; Locked rotor protection; Max number of starts/hour; Over voltage protection; Phase reversal protection; Power factor underload protection; PT-100 connection; PTC connection; Too long current limit protection; Too long start time protection; Under voltage protection; User defined protection; Voltage imbalance protectionWarning Details:Current imbalance warning; Current underload warning; Electronic overload Time-to-trip; EOL warning; Faulty fan warning; Locked rotor warning; Motor runtime limit warning; Over voltage warning; Phase loss warning (for standby); Power factor underload warning; Short circuit warning (for Limp mode); THD(U) - Total Harmonic Distortion warning; Thyristor overload warning (SCR); Under voltage warning; Voltage imbalance warning
Description
Rated Operating Voltage:
208 ... 690 V AC
Rated control supply voltage (U.)s):
100 ... 250 V AC
Rated control circuit voltage (Uc):
24 V DC
Rated Frequency (f):
50/60 Hz
Main Circuit 50 / 60 Hz
Rated Operating Power - Coaxial Connection (PE):
(230 V) 160 kW
(400 V) 315 kW
(500 V) 400 kW
(690 V) 560 kW
Rated Operating Current - Coaxial Connection (IE):
570 A
Rated Operating Power - Inner Delta Connection:
at 230 V 295 kW
at 400 V 540 kW
at 500 V 700 kW
at 690 V 960 kW
Rated Operating Current - Inner Delta Connection:
987 A
Percentage of Safety Factor:
100 %
Overload Protection:
Built-in electronic overload protection
Integrated Electronic Overload:
Yes
Starting capacity at maximum rated current Ie:
4xIe for 10s
Slope Time:
1 ... 120 second [unit of time]
Initial voltage at start-up:
10 ... 99 %
Special Buck Ramps:
100 ... 10 %
Inner triangle connection switch:
be
Running Signal Relay:
be
Bypass Signal Relay:
Yes
Fault Signal Relays:
Yes
Overload Signal Relay:
be
Ready to start/standby signal indication ON (LED):
Green
Operational signal indication R (LED):
Green
Protection Signal Indication (LED):
Yellow
Fault Signal Indication (LED):
Red
Communication:
Modbus-RTU; Modbus-TCP; Ethernet-IP; EtherCAT; DeviceNet; CANopen; Profibus; Profinet; BACnet-IP; BACnet-MSTP
Ingress Protection:
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Terminal Type:
Main Circuit: Bars
Control circuit connection capacity:
Rigid 1 x 2.5 mm²
Power supply circuit connection capacity:
Rigid 1 x 2.5 mm²
Tightening torque:
Main Circuit 35 N·m
Product range:
PSTX570
Function:
Auto phase sequence detection
Automatic restart
Current limit
Current limit ramp
Dual current limit
Dynamic brake
Electricity metering
Electronic overload Time-to-cool
Emergency mode
Event log
Show more
Protection Functions:
Bypass open protection; Current imbalance protection; Current underload protection; Dual overload (separate overload for start and run); Earth fault protection / ground fault protection; Electronic overload protection, EOL; Extension IO failure protection; Fieldbus failure protection; HMI failure protection; Locked rotor protection; Max number of starts/hour; Over voltage protection; Phase reversal protection; Power factor underload protection; PT-100 connection; PTC connection; Too long current limit protection; Too long start time protection; Under voltage protection; User defined protection; Voltage imbalance protection
Warning Details:
Current imbalance warning; Current underload warning; Electronic overload Time-to-trip; EOL warning; Faulty fan warning; Locked rotor warning; Motor runtime limit warning; Over voltage warning; Phase loss warning (for standby); Power factor underload warning; Short circuit warning (for Limp mode); THD(U) - Total Harmonic Distortion warning; Thyristor overload warning (SCR); Under voltage warning; Voltage imbalance warning